Icinga/ Nagios check command for NUT/ UPSC uninterruptible power supply.
You can not select more than 25 topics Topics must start with a letter or number, can include dashes ('-') and can be up to 35 characters long.
onkobu 6d50f861dc Re-enable upcs command check 5 months ago
eaton-samples Initial commit, version 1.0.0 2 years ago
other-samples Enable float values and locale setting 5 months ago
LICENSE Initial commit 2 years ago
README.md Enable float values and locale setting 5 months ago
check_upsc.sh Re-enable upcs command check 5 months ago

README.md

check_upsc

Icinga/ Nagios check command for NUT/ UPSC uninterruptible power supply.

Check UPSC

check_upsc [-h]
check_upsc -V
check_upsc [-t <test-file>] 
check_upsc [-d <device>] [OPTIONS]

-h             - print usage and exit
-V             - print version and exit
-t <test-file> - read properties from given file
-d <device>    - device that will be queried by command

Options:

-v             - verbose output
-b <percent>   - Warning threshold, value battery.charge
-r <seconds>   - Warning threshold, value battery.runtime
-l <locale>    - Locale, for example C to use . as float separator

It is not possible to override critical threshold as they
are determined by the UPS/ its driver. These thresholds force
a shutdown and masking them with monitoring values is
dangerous.

Preconditions

  1. Get a uninterruptiple power supply that is supported by Linux/ NUT/ upsc (see links below)
  2. Setup Network UPS Tools
  3. Verify ''upsc'' prints the correct values (have a look at the folder eaton-samples)
  4. Copy this script to a local directory, e.g. /usr/local/lib64/icinga2/plugins/ (local plugin directory)
  5. Create a check command in your Icinga2 configuration
  6. Assign this check command with a Icinga2 service definition to the responsible host
  7. Enjoy UPS-aware Icinga 2
# /etc/icinga2/conf.d/constants
#
const PluginLocalDir="/usr/local/lib64/icinga2/plugins"

# /etc/icinga2/conf.d/commands.conf
#
object CheckCommand "check-upsc-local" {
	command = [ PluginLocalDir + "/check_upsc.sh" ]
	arguments = {
		"-d" = {
			value = "YOURDevice@localhost"
			description = "The device supplying power in case of line failure"
			required = true
		}
		"-b" = {
			value = "$battery_charge_warning$"
			description = "Battery charge in percent that does not trigger WARNING yet"
			required = false
		}
		"-r" = {
			value = "$battery_runtime_warning$"
			description = "Remaining runtime in seconds that does not trigger WARNING yet"
			required = false
		}
	}
}

# /etc/icinga2/conf.d/services.conf

apply Service "upsc" {
	import "generic-service"
	# see /usr/share/icinga2/include/plugins-contrib.d/hardware.conf
	# and local adaption in commands.conf
	check_command = "check-upsc-local"
	
    # default values shown
	#vars.battery_charge_warning = "50"
	#vars.battery_runtime_warning = "300"

	assign where host.name == NodeName
}

Bonus:

Setup PNP4Nagios to graph the output, too.

Testing

With parameter -t a file can be injected instead of reading command output. Use this if your device yields an output that does not pass the check script successfully. Compare with samples in eaton-samples for the details.

# test run with an output that was recording with
# low battery and pending forced shutdown
#
check_upsc.sh -t eaton-samples/status_bat_fsd

Hints

  • Standard setup of NUT renders log messages with substring UPS
  • upsmon or upsdrv sometimes die or loose connection, output then becomes Stale Data
  • Depending on the UPS critical thresholds cause system shutdown automatically thus no critical thresholds can be set through the plugin